SIEMENS NXAirS-12 kV Air Insulation Withdrawable Metal-clad medium-voltage Switchgear
1. Characteristics
· Mechanical dynamic position indicator
· The closing/opening status of disconnecting switch and grounding switch can be indicated respectively on mechanical dynamic position indicator.
· Operating handle socket and control elements are obviously set adjacent to closing/opening indicator of controlled switches.
· All the switch operations can be carried out when high-voltage compartment door closed.
· All the parts and components installation heights meet the requirements of human engineering.
· Options: Capacitive electric indicator can be used to detect feeder or power of busbar.
2. Electric Parameters
- Rated voltage  | 
kV  | 
7.2  | 
12  | 
|
- Rated frequency  | 
Hz  | 
50  | 
50  | 
|
- Rated short-time power frequency withstand voltage (interphase, to-ground)  | 
kV  | 
32  | 
42  | 
|
- Rated lightning impulse withstand voltage (interphase, to-ground)  | 
kV  | 
60  | 
75  | 
|
- Rated short-circuit breaking current  | 
MAX  | 
kA  | 
40*  | 
40*  | 
- Rated short-time withstand current, 4s  | 
MAX  | 
kA  | 
40*  | 
40*  | 
- Rated short-circuit closing current  | 
MAX  | 
kA  | 
100*  | 
100*  | 
- Rated peak withstand current  | 
MAX  | 
kA  | 
100*  | 
100*  | 
- Rated bus current  | 
MAX  | 
A  | 
4000  | 
4000  | 
- Feeder current1)  | 
A  | 
|||
Circuit breaker cabinet  | 
4000  | 
4000  | 
||
Contactor cabinet  | 
250  | 
160  | 
||
Disconnecting handcart cabinet  | 
4000  | 
4000  | 
||
Bus segment cabinet  | 
4000  | 
4000  | 
||
Bus lifting cabinet  | 
4000  | 
4000  | 
||
· *: It is applicable to switchgears outside of contactor cabinet.
3. Overall Dimensions
| 
 Width mm  | 
Circuit breaker cabinet  | 
|
≤630A  | 
650  | 
|
1250A~2500A  | 
800  | 
|
3150A~4000A  | 
1000  | 
|
Disconnecting handcart cabinet  | 
||
≤2500A  | 
800  | 
|
3150A~4000A  | 
1000  | 
|
Transformer used in substation  | 
1000  | 
|